Inverters
Xantrex Datacom Inverter (XDI)

 

Modular Inverter System for Uninterruptible AC Power
The Xantrex Datacom Inverter (XDI) provides uninterruptible AC power to equipment connected to 48 volt DC battery banks in telecom environments. The modular Xantrex XDI consists of a compact, true sine-wave 2000 VA inverter module rated for continuous duty. It conveniently fits into standard 19-inch equipment racks and is easily scalable by adding parallel-connected modules.


XDI modules can be set up in a rack alongside the equipment it provides AC power to - offering the convenience of installing and servicing one system versus a number of independent systems. Also, with its hot swappable feature and capability to be configured in a N+1 redundant system, the XDI eliminates the frustration of unanticipated server down time and ensures continuity of service during mains power outages.


Features

  • Compact size (1 U)

  • Power share in parallel system for up to 20 kVA (10 units) of AC power

  • 3 kW, 4 kVA (5 s) surge capability

  • Short circuit proof

  • Rack mounted back plane to accommodate DC input and AC output connectors

  • High performance noise filters on both input and output

  • UL, CSA, CE, NEBS, FCC class B approvals


Option

TCP/IP enabled Ethernet port card

 

Specifications

 

Electrical & Mechanical Specifications

 

Output voltage*

 

120 VAC / 60 Hz

 

Voltage regulation

 

<-10% / +4% over full operating range

 

Frequency stability

 

+/- 0.05%

 

Efficiency

 

85% minimum

 

Output wave form

 

True sinusoidal

 

Power rating

 

2 kVA / 1.5 kW max, over full operating temperature range

 

Peak output current

 

50 A

 

Crest factor

 

2.8 at full load

 

Total harmonic distortion

 

<3%

 

Nominal input

 

-48 VDC

 

Input range

 

-40 - -60 VDC

 

Maximum input current

 

90 A (at 40 V in, max 3 kW surge output, 5 s max)

 

Input conducted noise voltage

 

<10 mVrms from 10 kHz - 10 mHz

 

Safe input range

 

0 - -80 VDC

 

DC input filtering

 

<32 dBrnc

 

Environmental & Physical Specifications

 

Operating temperature range

 

32° F to 122° F (0° C to 50° C) no derating

 

Storage temperature range

 

-58° F to 185° F (-50° C to 85° C)

 

Humidity range

 

maximum 95%, non-condensing

 

Module dimensions (H x W x D)

 

1.7 x 16.8 x 15.7" (43.2 x 426.7 x 398.8 mm)

 

Weight

 

22 lb (10 kg)

 

Regulatory Approvals

 

UL, CSA, CE, NEBS, FCC class B

 

Note: Specifications subject to change without notice.

*Contact factory for 220/230 VAC 50 Hz version.

 

 

 