|
How Does Impulse Winding Tester work ??
|
|
The impulse coil- winding tester tests the electrical characteristics of coil winding
without damaging the sample. The prerequisite conditions for quality of a coil
can be detected at just a glance. The detection is carried out when the same
electric impulse by capacitor discharge is applied to the master and the test coils.
The voltage decay waveform is generated in response to the impulse, related to
the Q- factor and inductance (impedance) of the coil. In this sense, the tester can
detect turn & layer short, the differences in the number of turns and the material
of the core. If high impulse voltage is applied, the poor insulation will appear as
a corona or layer discharge.
| |
|
1. AREA SIZE COMPARISON
This compares each area size of the master coil and the sample coil waveforms in the
intentionally determined zone. In Fig. 1, the area size is calculated between ‘a’ and ‘b’, an d
OK/ NG (Pass/ Fail) is determined by comparing the area size (i. e. what percent (%) the sample
waveform’s area size differs from that of the master waveform). The detecting criterion is set
by %. When the result is within the set value in %, the test coil is considered to be "OK". The area size of the wave is nearly proportional to the energy loss in the coil; therefore, the test
coil is considered to be OK/ NG by the amount of its energy loss. For example, when a
sample coil layer has a short circuit, the short circuit area is reflected as an increase of energy
loss.
2. DIFFERENTIAL AREA COMPARISON
This calculates the area size of differential portion between the master coil and the sample coil
waveforms in the intentionally determined zone. In Fig. 2, the differential area size is
calculated between ‘a’ and ‘b’, and OK/ NG is judged by detecting how large the differential
area size is. The detecting criterion is set by %. When the result is within the set value
in %, it is considered to be "OK". The differential area size represents the L value and total
energy loss. This method is especially effective, for example, when the change of the L value
causes ma jor problems.
3. CORONA DISCHARGE (FLUTTER VALUE) DETECTION
Regardless of the difference in waveforms, this method only detects the high frequency energy of corona discharge as shown in Fig. 3. It detects the corona value in the intentionally determined zone of the waveform, and judges OK/ NG by the corona evaluation value. The detecting criterion is set by an integer. The result that appears within the range is considered to be "OK". The wave is converted by derivative calculation and its area size is calculated. In an equivalent analog circuit, the energy value of the wave that passes through high pass filter is measured.
4. CORONA DISCHARGE (LAPLACIAN VALUE) DETECTION
The Laplacian is a method in digital filter processing used for detecting the edge intensity of an
image. In the application to the Flutter Value, it measures the 2 nd
derivative of the image to
find and extract the partial discharge. The discontinuity of the value hidden in the wave data
(noise) can be digitized, offering an easier detection of the partial discharge (Fig. 4).
5. VISUAL COMPARISON
The superimposed master and sample waves are displayed on the screen. This allows an easy
observation of the differences in characteristics of the two coils.
|
|